EasyManua.ls Logo

YASKAWA GA500 GA50U Series

YASKAWA GA500 GA50U Series
524 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.12 n: Special Adjustment
94 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
No.
(Hex.)
Name Description
Default
(Range)
n8-26
(0559)
Expert
ACR d Gain @PoleEst
Sets the proportional gain for current regulator d-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
500
(0 - 2000)
n8-27
(055A)
Expert
ACR d Integral Time
@PoleEst
Sets the integral time for current regulator d-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
n8-28
(055B)
Expert
ACR d Lim @PoleEst
Sets the d-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
100%
(0 - 150%)
n8-35
(0562)
Initial Pole Detection
Method
Sets how the drive detects the position of the rotor when the motor starts.
Note:
When you use an SPM motor, set n8-35 = 0. When you use an IPM motor, set n8-35 = 0 to 2.
When you set n8-35 = 1, do High Frequency Injection Auto-Tuning.
0 : Pull-in
1 : High Frequency Injection
2 : Pulse Injection
Determined by A1-02
(0 - 2)
n8-36
(0563)
HFI Frequency Level for L
Tuning
Sets the injection frequency for high frequency injection.
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI
Overlap Selection = Enabled] to enable this parameter.
The drive automatically calculates this value when High Frequency Injection Auto-Tuning
completes successfully.
500 Hz
(200 - 1000 Hz)
n8-37
(0564)
Expert
HFI Voltage Amplitude
Level
Sets the high frequency injection amplitude as a percentage where 200 V = 100% for 200 V class
drives and 400 V = 100% for a 400 V class drives. Usually it is not necessary to change this setting.
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI
Overlap Selection = Enabled] to enable this parameter.
The drive automatically calculates this value when High Frequency Injection Auto-Tuning
completes successfully.
20.0%
(0.0 - 50.0%)
n8-39
(0566)
HFI LPF Cutoff Freq
Sets the low-pass filter shut-off frequency for high frequency injection.
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI
Overlap Selection = Enabled] to enable this parameter.
The drive automatically calculates this value when High Frequency Injection Auto-Tuning
completes successfully.
250 Hz
(0 - 1000 Hz)
n8-41
(0568)
Expert
HFI P Gain
Sets the response gain for the high frequency injection speed estimation.
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI
Overlap Selection = Enabled] to enable this parameter.
When A1-02= 6 [Control Method Selection = AOLV/PM] and you do High Frequency Injection
Auto-Tuning, the drive automatically sets this parameter .
2.5
(-10.0 - +10.0)
n8-42
(0569)
Expert
HFI I Time
Sets the integral time constant for the high frequency injection speed estimation. Usually it is not
necessary to change this setting.
0.10 s
(0.00 - 9.99 s)
n8-45
(0538)
Speed Feedback Detection
Gain
Sets the internal speed feedback detection reduction unit gain as a magnification value. Usually it is
not necessary to change this setting.
0.80
(0.00 - 10.00)
n8-46
(0539)
Expert
PM Phase Compensation
Gain
Sets the gain to compensate for phase differences. Usually it is not necessary to change this setting.
0.3
(0.0 - 10.0)
n8-47
(053A)
Pull-in Current Comp Filter
Time
Sets the time constant the drive uses to align the pull-in current reference value with the actual
current value. Usually it is not necessary to change this setting.
5.0 s
(0.0 - 100.0 s)
n8-48
(053B)
RUN
Pull-in/Light Load Id
Current
On the basis that parameter E5-03 [Motor Rated Current (FLA)] is the 100% value, this parameter
sets the d-axis current that flows to the motor during run at constant speed as a percentage.
30%
(0 - 200%)
n8-49
(053C)
RUN
Expert
Heavy Load Id Current
Sets the d-axis current to that the drive will supply to the motor to run it at a constant speed with a
heavy load. Considers E5-03 [PM Motor Rated Current (FLA)] to be 100%. Usually it is not
necessary to change this setting.
Determined by E5-01
(-200.0 - +200.0%)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Related product manuals