2-1
Verify wires are properly connected and no erroneous grounds exist.
• Remove all debris from the Drive enclosure, such as loose wire clippings, metal shavings, etc.
Verify all mechanical connections inside the Drive are tight.
Verify motor is not connected to load.
• Apply input power only after the front cover is in place. DO NOT remove the front cover or Digital
Operator while input power is on.
• Determine the proper control method for the application.
Open Loop
Vector Control - Use section 2.2 for startup instructions
Parameter n002 = 1. Open Loop Vector Control method should be used for
most constant torque applications of the Drive. With this control method
there is excellent starting torque and excellent speed regulation. The startup
procedure for this control method is slightly more complicated.
V/f Contr
ol - Use section 2.3 for startup instructions
Parameter n002 = 0. V/f control should be used for most variable torque
applications. Variable torque applications would include: fan, blower,
centrifugal pump, and mixers. Generally variable torque loads do not require
high levels of starting torque. V/f control can also be used for some constant
torque loads where starting torque and speed regulation are not critical.
2.1 PRE-POWER CHECKS
Section 2. INITIAL START-UP

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA GPD315/V7-4X and is the answer not in the manual?

YASKAWA GPD315/V7-4X Specifications

General IconGeneral
BrandYASKAWA
ModelGPD315/V7-4X
CategoryDC Drives
LanguageEnglish

Related product manuals