6-1
This section describes the alarm and fault displays, explanations for fault conditions and corrective
actions to be taken if the Drive malfunctions.
A failure in the Drive can fall into one of two categories, Alarm or Fault.
A blinking “Alarm” indication is a warning that a Drive trouble condition will soon occur, or that a
programming error has been made. The Drive will continue to operate during an “Alarm” indication.
A blinking “Minor Fault” indication is displayed during less serious faults, or when a problem exists in
the external circuitry. The Drive will continue to operate, and a “Minor Fault” contact will be closed if a
multi-function output is programmed for the condition.
A steady “Major Fault” indication is displayed when the Drive’s Fault relay has tripped. The motor
coasts to a stop, and a fault signal output is present at control circuit terminals 18-20.
Section 6. FAULT DIAGNOSIS AND CORRECTIVE ACTIONS
6.1 GENERAL
Alarm Display
Digital RUN (Green)
Drive
Explanation
Causes and
Operator ALARM (Red)
Status Corrective Actions
UV (Main circuit low voltage) Check the following:
Main circuit DC voltage Power supply voltage
drops below the low-voltage Main circuit power
detection level while the supply wiring is
drive output is OFF. connected.
230V: Stops at main circuit Terminal screws are
DC voltage below securely tightened.
Blinking approx. 200V
(160V for single-
phase)
460V: Stops at main circuit
DC voltage below
approx. 400 V
OV (Main circuit overvoltage) Check the power supply
Warning
Main circuit DC voltage voltage.
only.
exceeds the over voltage
Fault
detection level while the
Blinking
contacts
drive output is OFF.
do not
Detection level: approx.
change
410V or more (approx.
state.
820V for 460V class).
OH (Cooling fin overheat) Check the intake air
Intake air temperature temperature.
Blinking
rises while the drive
output is OFF.
Warning. OH3 (Drive overheat Release the input of
Fault pre-alarm) inverter overheat pre-
contacts OH3 signal is input. alarm signal.
do not
Blinking
change
state.
Table 6-1. Alarm Displays and Corrective Actions
: ON : BLINKING : OFF