5-36
D. n115 : Stall Prevention Above Base Speed During Running Factory setting: 0
Range: 0 or 1
Setting Function
0 Disabled (level is based on setting of n094)
1 Enabled (level at Fmax, n011, is n094 x 0.4)
E. n116 : Stall Prevention During Run, Accel/Decel Time Select Factory setting: 0
Range: 0 or 1
Setting Function
0 Follows accel/decel #1 (n019, n020) or accel/decel #2
(n021,n022)
Note: Multi-Function input selectable
1 Follows accel/decel #2 (n021,n022) always
5.23 STALL PREVENTION