EasyManua.ls Logo

YASKAWA HV600 Series - 5 Common Drive Specifications

YASKAWA HV600 Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Common Drive Specifications
12 YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation
Model
Maximum Applicable Motor Output
kW (HP)
Rated Output Current
A
4096 56 (75) 96
4124 75 (100) 124
4156 93 (125) 156
4180 112 (150) 180
4240 150 (200) 240
4302 186 (250) 302
5 Common Drive Specifications
Note:
To get the longest product life, install the drive in an environment that meets the necessary specifications.
Table 5.1 Control Characteristics
Item Specification
Control Methods
V/f Control (V/f)
PM Open Loop Vector Control (OLV/PM)
EZ Open Loop Vector Control (EZOLV)
Frequency Control
Range
EZOLV: 0.01 Hz to 120 Hz
V/f and OLV/PM: 0.01 Hz to 400 Hz
Frequency Accuracy
(Temperature
Fluctuation)
Digital inputs: Within ±0.01% of the maximum output frequency (-10 °C to +40 °C (14 °F to 104 °F))
Analog inputs: Within ±0.1% of the maximum output frequency (25 °C ±10 °C (77 °F ±18 °F))
Frequency Setting
Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output frequency (11-bit)
Output Frequency
Resolution
0.001 Hz
Frequency Setting
Signal
Main speed frequency reference: 0 Vdc to 10 Vdc (20 kΩ), 4 mA to 20 mA (250 Ω), 0 mA to 20 mA (250 Ω)
Starting Torque
V/f: 140%/3 Hz
OLV/PM: 100%/10% speed
EZOLV: 100%/10% speed
Speed Control Range
For Induction Motors:
V/f: 1:40
EZOLV: 1:10
For Permanent Magnet Motors and Synchronous Reluctance Motors:
OLV/PM: 1:20
EZOLV: 1:10
Torque Limits
Parameter settings allow different limits in four quadrants in EZOLV control method.
Accel/Decel Time
0.1 s to 6000.0 s
The drive can set two pairs of different acceleration and deceleration times.
V/f Characteristics
Select from 15 pre-defined V/f patterns, or a user-set V/f pattern.
Main Control
Functions
Restart After Momentary Power Loss, Speed Search, Overtorque/Undertorque Detection, Torque Limit, 8 Step Speed (max.), Accel/Decel Switch, S-curve
Acceleration/Deceleration, 3-wire Sequence, Auto-Tuning (Rotational and Stationary), Cooling Fan ON/OFF Switch, Slip Compensation, Torque
Compensation, Jump Frequency, Upper/Lower Limits for Frequency Reference, DC Injection Braking at Start and Stop, Overexcitation Braking, High Slip
Braking, PID Control (with Sleep Function), Energy Saving Control, APOGEE FLN Communication (RS-485 4.8 kbps), BACnet Communication (RS-485
max. 76.8 kbps), MEMOBUS/Modbus Communication (RS-485 max. 115.2 kbps), Metasys N2 Communication (RS-485 9.6 kbps), Auto Restart, Application
Presets, DriveWorksEZ (customized functions), KEB, Overexcitation Deceleration, Overvoltage Suppression
Table 5.2 Protection Functions
Item Specification
Motor Protection
Electronic thermal overload protection
Momentary
Overcurrent
Protection
Drive stops when the output current is more than 175% of the drive rated output current.

Table of Contents

Related product manuals