YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation 77
Table 12.4 Control Circuit Terminal Power Supplies
Input/Output Terminals Power Supply Specifications
Digital input S1 to S7, SN, SC, SP
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Analog input A1 to A2, AC, +V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Analog output FM, AM, AC Uses the LVLC power supply in the drive.
Safe disable input H1, H2, HC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Serial communication input/output D+, D-, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
24 V external power supply input/output PS, AC, +P Use the UL Listed class 2 power supply.
Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National Electric Code (NEC) and the
Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and L1-01 through L1-04 [Motor Overload Protection Select] correctly to enable motor
overload and overheat protection.
Refer to the control method and set the motor rated current with E2-01 [Motor Rated Current (FLA)], E5-03 [PM
Motor Rated Current (FLA)], or E9-06 [Motor Rated Current (FLA)].
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04
(10% to 200% of the drive
rated current)
Note:
If E2-01 < E2-03 [Motor No-Load Current] the drive will detect oPE02 [Parameter Range Setting Error].
The default settings and setting ranges are in these units:
0.01 A: 2011 to 2046, 4005 to 4014
0.1 A: 2059 to 2273, 4021 to 4302
The value set for E2-01 becomes the reference value for motor protection and the torque limit. Enter the motor rated
current as written on the motor nameplate. The value of E2-01 is automatically set to the value input for Motor Rated
Current by the Auto-Tuning process.
E5-03: PM Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E5-03
(032B)
PM Motor Rated Current
(FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
0.01 A: 2011 to 2046, 4005 to 4014
0.1 A: 2059 to 2273, 4021 to 4302
The drive automatically sets E5-03 to the value input for PM Motor Rated Current after you do these types of Auto-
Tuning:
PM Motor Parameter Settings
PM Stationary Auto-Tuning
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV