EasyManua.ls Logo

YASKAWA HV600 Series - EMC Directive; Install a Drive to Conform to the EMC Directive

YASKAWA HV600 Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13 European Standards
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation 85
EMC Directive
Drives with built-in EMC filters were tested in accordance with European standard IEC/EN 61800-3:2004/A1:2012,
and comply with the EMC Directive.
Install a Drive to Conform to the EMC Directive
Use this procedure to install drives that comply with the EMC Directive when the drive is a single unit or installed in
a larger device.
1. Install the drive on a grounded metal plate.
2. Wire the drive and motor.
3. Ground the wire shielding on the drive side and motor side.
A - Drive
B - 100 m (328 ft) maximum
C - Motor
D - Metal conduit
E - Grounding wire
Figure 13.3 Wiring the Drive and Motor
Note:
Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
The maximum wiring length between the drive and motor is 100 m (328 ft). Keep the wire as short as possible.
Keep the grounding wire as short as possible.
4. Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.
A - Braided shield cable
B - Metal plate
C - Cable clamp (conductive)
Figure 13.4 Ground the shield

Table of Contents

Related product manuals