10 Drive Start-Up Procedure
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation 65
Table 10.9 MFAI Terminals A1 and A2 Signal Settings
Terminal Types of Input Signals Jumper Switch S1
Parameter
No. Signal Level
A1
Voltage input
(Default)
H3-01
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
Current input
2: 4 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
A2
Voltage input
H3-09
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
Current input
(Default)
2: 4 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
Note:
Set H3-02, H3-10 = 0 [Terminal A1 Function Selection, Terminal A2 Function Selection = Frequency Reference] to set A1 and A2 to
frequency reference. The drive will add the analog input values together to make the frequency reference.
Set Output Signals for MFAO Terminals FM, AM
Set the signal type for terminals AM and FM to voltage or current output. Use jumper switch S5 and H4-07, H4-08
[Terminal FM Signal Level Select, Terminal AM Signal Level Select] to set the signal type.
Figure 10.10 Location of Jumper Switch S5
Terminal Types of Output Signals Jumper Switch S5
Parameter
No. Signal Level
FM
Voltage output
(Default)
H4-07
0: 0 V to 10 V
Current output 2: 4 mA to 20 mA
AM
Voltage output
(Default)
H4-08
0: 0 V to 10 V
Current output 2: 4 mA to 20 mA
Switch ON Termination Resistor for RS-485 Communications
When the drive is the last slave in these communications, set DIP switch S2 to the ON position:
APOGEE FLN
BACnet
MEMOBUS/Modbus
Metasys N2
This drive has a built-in termination resistor for the RS-485 interface.