6 Mechanical Installation
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation 17
A - 50 mm (2 in) minimum
B - 2 mm (0.08 in) minimum
C - 2 mm (0.08 in) minimum
D - 300 mm (11.8 in) minimum
E - 120 mm (4.7 in) minimum
Figure 6.3 Installation Distances for More than One Drive (Side-by-Side)
Note:
Align the tops of drives that have different dimensions to help when you replace cooling fans.
Figure 6.4 IP20/UL Type 1 Drives Installed Side-by-Side
Installing More than One Drive Adjacent to Each Other without Derating
Use the clearances specified in Figure 6.5. Make sure that there is sufficient space.