10 Drive Start-Up Procedure
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation 63
Switches and Jumpers on the Terminal Board
The terminal board has switches to adapt the drive I/Os to the external control signals as shown in Figure 10.8.
Set the switches to select the functions for each terminal.
Figure 10.8 Locations of Switches
Table 10.8 I/O Terminals and Switches Functions
Position Switch Terminal Function Default Setting
A Jumper switch S1 A1, A2 Sets terminals A1 and A2 to voltage or current output.
A1: V (voltage input)
A2: I (current input)
B Jumper switch S5 FM, AM Sets terminals FM and AM to voltage or current output.
FM: V (voltage output)
AM: V (voltage output)
C DIP switch S2 -
Enables and disables the termination resistor of these
communications:
APOGEE FLN
BACnet
MEMOBUS/Modbus
Metasys N2
OFF
Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
MFDI (terminals S1 to S7)
MFDO (terminals M1 to M6)
MFAI (terminals A1, A2)
MFAO (terminals FM, AM)