7 Electrical Installation
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation 27
Figure 7.1 Standard Drive Connection Diagram
*1 Set the wiring sequence to de-energize the drive with the fault relay output. If the drive outputs a fault during fault restart when you use
the fault restart function, set L5-02 = 1 [Fault Contact at Restart Select = Always Active] to de-energize the drive. Be careful when you
use a cut-off sequence. The default setting for L5-02 is 0 [Active Only when Not Restarting].
*2 Use branch circuit protection devices as recommended in this manual.
*3 Cooling fan wiring is not necessary for self-cooling motors.
*4 Connect DC power supply input to terminals - and +1.
WARNING
Fire Hazard. Only connect factory-recommended devices or circuits to drive terminals - and +1. Do not
connect AC power to these terminals. Incorrect wiring can cause damage to the drive and serious injury or death from fire.