11 Drive Control and Programming
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation 69
No.
(Hex.)
Name Description
E1-04
(0303)
Maximum Output Frequency
Sets the maximum output frequency for the V/f pattern.
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
E1-09
(0308)
Minimum Output Frequency
Sets the minimum output frequency for the V/f pattern.
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
E2-11
(0318)
Motor Rated Power
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
H1-01 - H1-07
(0438, 0439, 0400 -
0404)
Terminal S1 to S7 Function
Selection
Sets the functions for MFDI terminals S1 to S7.
H2-01
(040B)
Term M1-M2 Function Selection
Sets the function for MFDO terminal M1-M2.
H2-02
(040C)
Term M3-M4 Function Selection
Sets the function for MFDO terminal M3-M4.
H3-01
(0410)
Terminal A1 Signal Level Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
H3-02
(0434)
Terminal A1 Function Selection
Sets the function for MFAI terminal A1.
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
H3-09
(0417)
Terminal A2 Signal Level Select
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
H3-10
(0418)
Terminal A2 Function Selection
Sets the function for MFAI terminal A2.
H3-11
(0419)
RUN
Terminal A2 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A2.
H3-12
(041A)
RUN
Terminal A2 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A2.
H3-13
(041B)
Analog Input FilterTime Constant
Sets the time constant for primary delay filters on MFAI terminals.
H3-14
(041C)
Analog Input Terminal Enable Sel
Sets which terminal or terminals to enable when H1-xx = C [MFDI Function Selection = Analog Terminal Enable
Selection] is activated.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
H4-01
(041D)
Terminal FM Analog Output Select
Sets the monitor number to send from MFAO terminal FM.
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV
V/f
OLV/PM OLV/PM
EZOLV