12 UL Standards
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation 73
Model Terminals
Recommended
Gauge
AWG, kcmil
Ferrule
*1
Crimp Terminal Part Number
Manufacturer: PANDUIT Corp.
Type LCA Type P Type S
2143
R/L1, S/L2, T/L3 2/0 N/A LCA2/0-56-X N/A S2/0-56R-X
U/T1, V/T2, W/T3 3/0 N/A LCA3/0-56-X N/A S3/0-56R-5
-, +1 3/0 N/A LCA3/0-56-X N/A S3/0-56R-5
4 N/A LCA4-56-L P4-56R-E S4-56R-E
2169
R/L1, S/L2, T/L3 3/0 N/A LCA3/0-56-X N/A S3/0-56R-5
U/T1, V/T2, W/T3 4/0 N/A LCA4/0-56-X N/A S4/0-56R-5
-, +1 1/0 × 2 N/A LCA1/0-56-X N/A S1/0-56R-X
4 N/A LCA4-56-L P4-56R-E S4-56R-E
2211
R/L1, S/L2, T/L3 1/0× 2 N/A LCA1/0-12-X N/A S1/0-12R-X
U/T1, V/T2, W/T3 1/0× 2 N/A LCA1/0-12-X N/A S1/0-12R-X
-, +1 1/0× 2 N/A LCA1/0-12-X N/A S1/0-12R-X
3 or 2 N/A
LCA4-12-L
or
LCA2-12-Q
P2-12R-X
*2
S2-12R-X
*2
2273
R/L1, S/L2, T/L3 2/0 × 2 N/A LCA2/0-12-X N/A
S2/0-76R-X
or
S2/0-12R-X
U/T1, V/T2, W/T3 2/0 × 2 N/A LCA2/0-12-X N/A
S2/0-76R-X
or
S2/0-12R-X
-, +1 3/0 × 2 N/A LCA3/0-12-X N/A
S3/0-76R-5
or
S3/0-12R-5
2 N/A LCA2-12-Q P2-12R-X S2-12R-X
4005
R/L1, S/L2, T/L3 14 F80-10 N/A N/A N/A
U/T1, V/T2, W/T3 14 F80-10 N/A N/A N/A
-, +1 14 F80-10 N/A N/A N/A
14 N/A LCA10-14-L P10-14R-L N/A
4008
R/L1, S/L2, T/L3 14 F80-10 N/A N/A N/A
U/T1, V/T2, W/T3 14 F80-10 N/A N/A N/A
-, +1 14 F80-10 N/A N/A N/A
14 N/A LCA10-14-L P10-14R-L N/A
4011
R/L1, S/L2, T/L3 14 F80-10 N/A N/A N/A
U/T1, V/T2, W/T3 14 F80-10 N/A N/A N/A
-, +1 14 F80-10 N/A N/A N/A
12 N/A LCA10-14-L P10-14R-L N/A
4014
R/L1, S/L2, T/L3 14 F80-10 N/A N/A N/A
U/T1, V/T2, W/T3 12 F81-10 N/A N/A N/A
-, +1 12 F81-10 N/A N/A N/A
10 N/A LCA10-14-L P10-14R-L N/A