5.6.5.2 Count once
5.6.5.2.1
No main counting direction
n The counter counts once starting with load value.
n It is counted forward or backward.
n The counter limits are fix set to maximum range.
n At over- or underflow at the count limits, the counter jumps to the according other
count limit and the gate is automatically closed.
n T
o restart the count process, you have to generate an edge 0-1 at the gate
Ä
Chapter
5.6.6.2 ‘Gate function’ on page 111.
n With the configured ‘Gate function’ ‘Interrupt count’ the counting is continued with
current Counter value.
n With configured ‘Gate function’ ‘Cancel count’ the counter starts with the Load value.
Limits Valid range of values
Lower count limit
-2 147 483 648 (-2
31
)
Upper count limit
+2 147 483 647 (2
31
-1)
Interrupting gate control
Aborting gate control
VIPA System MICRO
Deployment I/O periphery
Counting > Counter operating modes
HB400 | CPU | M13-CCF0000 | en | 16-47 105