2.5 Wiring
CAUTION!
Consider temperature for external cables!
Cables may experience temperature increase due to system heat dissi-
pation. Thus the cabling specification must be chosen 5°C above ambient
temperature!
CAUTION!
Separate insulation areas!
The system is specified for SEL
V/PELV environment. Devices, which are
attached to the system must meet theses specifications. Installation and
cable routing other than SELV/PELV specification must be separated
from the system’s equipment!
2.5.1 Wiring CPU
For wiring the CPU has removable connectors. With the wiring of the connectors a "push-
in" spring-clip technique is used. This allows a quick and easy connection of your signal
and supply lines. The clamping of
f takes place by means of a screwdriver.
U
max
240V AC / 30V DC
I
max
10A
Cross section
0.2 ... 1.5mm
2
(A
WG 24 ... 16)
Stripping length 10mm
Use for wiring rigid wires respectively use wire sleeves. When using stranded wires you
have to press the release button with a screwdriver during the wiring.
1 Labeling on the casing
2 Pin no. at the connector
3 Release area
4 Connection hole for wire
CPU connector
Data
Wiring procedure
VIPA System MICRO
Basics and mounting
Wiring > Wiring CPU
HB400 | CPU | M13-CCF0000 | en | 16-47 18