7.3 PtP communication via extension module EM M09
9pin SubD jack: (isolated)
Using the PtP functionality the RS485 interface is allowed to connect via serial point-to-
point connection to dif
ferent source res. target systems.
n Protocols:
– ASCII
– STX/ETX
– 3964R
– USS
– Modbus master (ASCII, RTU)
n Serial bus connection
– Full-duplex Four-wire operation (RS422)
– Half-duplex Two-wire operation (RS485)
– Data transfer rate: max 115 kBaud
A hardware configuration to enable the PtP functionality is not necessary.
1. Turn off the power supply.
2.
Mount the extension module.
Ä
Chapter 2.4 ‘Mounting’ on page 13
3. Establish a cable connection to the communication partner.
4. Switch on the power supply
.
ð
After a short boot time the interface X1 PtP is ready for PtP communication.
X1 PtP (RS422/485)
Enable PtP functionality
VIPA System MICRO
Option: PtP communication
PtP communication via extension module EM M09
HB400 | CPU | M13-CCF0000 | en | 16-47 157