EasyManua.ls Logo

YASKAWA VIPA System MICRO M13-CCF0000 - 4.11.2 Function security

YASKAWA VIPA System MICRO M13-CCF0000
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
n : After PowerON the yellow LED of the status bar blinks in the STOP
state.
n : After a short time the flashing changes to a steady light.
n During the transition from ST
OP to RUN a call is issued to the start-up organization
block OB 100.
The processing time for this OB is not monitored.
The START-UP OB may issue calls to other blocks.
All digital outputs are disabled during the START-UP, this means BASP is acti-
vated.
: The green LEDs blinks as soon as the OB 100 is operated and for
at least 3s, even if the start-up time is shorter or the CPU gets to ST
OP due to an
error.
: The green LEDs of the status bar lights up when the START-UP is
completed and the CPU is in the RUN state.
* OB 102 (Cold start)
If there is a "W
atchdog" error the CPU still remains in STOP state. With
such an error the CPU must be manually started again. For this the
OB 102 (cold start) must exist. The CPU will not go to RUN without the
OB 102. Alternatively you can bring your CPU in RUN state again by an
overall reset respectively by reloading your project.
Please consider that the OB 102 (cold start) may exclusively be used for
treatment of a watchdog error.
n
: The green LED lights up when the CPU is in the RUN state.
n The application program in
OB 1 is processed in a cycle. Under the control of alarms
other program sections can be included in the cycle.
n All timers and counters being started by the program are active and the process
image is updated with every cycle.
n BASP is deactivated, i.e. all outputs are enabled.
4.11.2 Function security
The CPUs include security mechanisms like a W
atchdog (100ms) and a parameterizable
cycle time surveillance (parameterizable min. 1ms) that stop res. execute a RESET at the
CPU in case of an error and set it into a defined STOP state. The VIPA CPUs are devel-
oped function secure and have the following system properties:
Event concerns Effect
RUN ® ST
OP general BASP (Befehls-Ausgabe-Sperre, i.e. command output lock)
is set.
central digital outputs The outputs are disabled.
central analog outputs The outputs are disabled.
n V
oltage outputs issue 0V
n Current outputs 0...20mA issue 0mA
n Current outputs 4...20mA issue 4mA
If configured also substitute values may be issued.
decentral outputs Same behaviour as the central digital/analog outputs.
Operating mode START-
UP
Operating mode RUN
VIPA System MICRO
Deployment CPU M13-CCF0000
Operating modes > Function security
HB400 | CPU | M13-CCF0000 | en | 16-47 74

Table of Contents

Related product manuals