9. Navigate in the hardware catalog to the directory ‘PROFINET IO
è Additional field devices è I/O è VIP
A MICRO PLC’ and connect the IO device
M13-CCF0000 to your PROFINET system.
ð
In the slot overview of the PROFINET IO device ‘VIPA MICRO PLC’ the CPU is
already placed at slot 0.
4.5 Hardware configuration - System MICRO modules
To connect System SLIO modules, the CPU has a backplane bus, which is supplied by
the CPU. Here up to 8 System MICRO modules can be connected.
1.
Perform, if not already done, a hardware configuration for the CPU.
Ä
Chapter 4.4
‘Hardware configuration - CPU’ on page 58
2. Starting with slot 1 place in the slot overview of the PROFINET IO device ‘VIPA
MICRO PLC’ your System MICRO modules in the plugged sequence.
3. Parametrize if necessary the modules and assign valid addresses, so that they can
directly be addressed.
System SLIO backplane
bus
Proceeding
VIPA System MICRO
Deployment CPU M13-CCF0000
Hardware configuration - System MICRO modules
HB400 | CPU | M13-CCF0000 | en | 16-47 60