The installation of the PROFINET IO devices ‘VIP
A MICRO PLC’ happens in the hard-
ware catalog with the following approach:
1. Go to the service area of www
.vipa.com.
2. Load from the download area at ‘PROFINET files’ the file Micro_Vxxx.zip.
3. Extract the file into your working directory
.
4. Start the Siemens hardware configurator
.
5. Close all the projects.
6.
Select ‘Options è Install new GSD file’
7. Navigate to your working directory and install the according GSDML file.
ð
After the installation according PROFINET IO device can be found at
‘PROFINET IO è Additional field devices è I/O è VIP
A MICRO PLC’
In the Siemens SIMATIC Manager the following steps should be executed:
1. Start the Siemens hardware configurator with a new project.
2. Insert a profile rail from the hardware catalog.
3. Place at ‘Slot’ -Number 2 the CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).
4. Click at the sub module ‘PN-IO’ of the CPU.
5.
Select ‘Context menu è Insert PROFINET IO System
.
6. Create with [New] a new sub net and assign valid address data
7. Click at the sub module ‘PN-IO’ of the CPU and open with ‘Context menu
è Properties’ the properties dialog.
8. Enter at ‘General’ a device name. The device name must be unique at the Ethernet
subnet.
Installing the IO device
VIP
A MICRO PLC
Proceeding
VIPA System MICRO
Deployment CPU M13-CCF0000
Hardware configuration - CPU
HB400 | CPU | M13-CCF0000 | en | 16-47 59