4 Deployment CPU M13-CCF0000
4.1 Assembly
Information about assembly and cabling
Ä
Chapter 2 ‘Basics and
mounting’ on page 10.
4.2 Start-up behavior
n The CPU checks whether a project AUT
OLOAD.WLD exists on the memory card. If
so, an overall reset is executed and the project is automatically loaded from the
memory card.
n The CPU checks whether a command file with the name VIPA_CMD.MMC exists on
the memory card. If so the command file is loaded from the memory card and the
commands are executed.
n After PowerON and CPU STOP the CPU checks if there is a *.pkg file (firmware file)
on the memory card. If so, this is shown by the status bar of the CPU and the firm-
ware may be installed by an update request.
Ä
Chapter 4.13 ‘Firmware update’
on page 76
n The CPU checks if a previously activated VSC is inserted. If not, this is shown by the
status bar of the CPU and a diagnostics entry is released. The CPU switches to
STOP after 72 hours. With a just installed VSC activated functionalities remain acti-
vated.
Ä
Chapter 4.19 ‘Diagnostic entries’ on page 85
After this the CPU switches to the operating mode, which is set on the operating mode
switch.
In the delivery state the CPU is overall reset. After a STOP®RUN transition the CPU
switches to RUN without program.
4.3 Addressing
4.3.1 Overview
To provide specific addressing of the installed peripheral modules, certain addresses
must be allocated in the CPU. This address mapping is in the CPU as hardware configu-
ration. If there is no hardware configuration, depending on the slot, the CPU assigns
automatically peripheral addresses for digital in-/output modules starting with 0 and
analog modules are assigned to even addresses starting with 256.
4.3.2 Default address assignment of the I/O part
Sub module Input address Access Assignment
AI5/AO2 800 WORD Analog input channel 0 (X6)
802 WORD Analog input channel 1 (X6)
Turn on power supply
Delivery state
VIPA System MICRO
Deployment CPU M13-CCF0000
Addressing > Default address assignment of the I/O part
HB400 | CPU | M13-CCF0000 | en | 16-47 56