5.3.3 Wiring
X6 Function Type LED Description
1 Sys DC 24V I
green
1L+: DC 24V for electronic section supply
2 Sys 0V I 1M: GND for electronic section supply
3 Shield I Shield
4 AGND I GND for analog inputs
5 AI 0 I Analog input AI 0
6 AI 1 I Analog input AI 1
7 DO 1.0 O
green
Digital output DO 8
8 DO 1.1 O
green
Digital output DO 9
9 DO 1.2 O
green
Digital output DO 10
10 DO 1.3 O
green
Digital output DO 11
For the analog signals you have to use isolated cables. With this the interferences can be
reduced. The shield of the analog cables should be grounded at both ends. If there are
potential differences between the cables, a potential compensation current can flow,
which could disturb the analog signals. In this case, you should only ground the shield at
one end of the cable.
Temporarily not used analog inputs must be connected to the concerning
ground.
5.3.4 Parametrization
5.3.4.1
Address assignment
Sub module Input address Access Assignment
AI5/AO2 800 WORD Analog input channel 0 (X6)
802 WORD Analog input channel 1 (X6)
X6: DC 24V, AI, DO byte 1
Cables for analog signals
VIPA System MICRO
Deployment I/O periphery
Analog input > Parametrization
HB400 | CPU | M13-CCF0000 | en | 16-47 89