Byte Bit 7...0
11 Diagnostic interrupt due to "process interrupt lost" at...
n Bit 0: ... input I+1.4
n Bit 1: 0 (fix)
n Bit 2: ... input I+1.5
n Bit 3: 0 (fix)
n Bit 4: ... input I+1.6
n Bit 5: 0 (fix)
n Bit 6: ... input I+1.7
n Bit 7: 0 (fix)
12 Diagnostic interrupt due to "process interrupt lost" at...
n Bit 0: End of measurement channel 0
(End of integration time)
n Bit 7 ... 1: 0 (fix)
13 Diagnostic interrupt due to "process interrupt lost" at...
n Bit 0: End of measurement channel 1
(End of integration time)
n Bit 7 ... 1: 0 (fix)
14 Diagnostic interrupt due to "process interrupt lost" at...
n Bit 0: End of measurement channel 2
(End of integration time)
n Bit 7 ... 1: 0 (fix)
15 Diagnostic interrupt due to "process interrupt lost" at...
n Bit 0: End of measurement channel 3
(End of integration time)
n Bit 7 ... 1: 0 (fix)
The record set 1 contains the 4byte of the record set 0 and additionally 12byte module
specific diagnostic data. The diagnostic bytes have the following assignment:
Byte Bit 7...0
0 ... 3
Content record set 0
Ä
‘Record set 0 Diagnostic
incoming
’ on page 132
4
n Bit 6 ... 0: Channel type (here 70h)
–
70h: Digital input
– 71h: Analog input
– 72h: Digital output
– 73h: Analog output
– 74h: Analog input/output
n Bit 7: More channel types present
– 0: no
– 1: yes
5 Number of diagnostic bits per channel (here 08h)
6 Number of channels of a module (here 08h)
Diagnostic record set 1 at
pulse width modulation
VIPA System MICRO
Deployment I/O periphery
Diagnostic and interrupt > Diagnostic interrupt
HB400 | CPU | M13-CCF0000 | en | 16-47 138