The PROFIBUS line has to be terminated with its ripple resistor. Please
make sure to terminate the last participants on the bus at both ends by
activating the terminating resistor
.
In PROFIBUS all participants are wired parallel. For that purpose, the bus cable must be
feed-through. V
ia the order number 972-0DP10 you may order the bus connector "Easy-
Conn" from VIPA. This is a bus connector with switchable terminating resistor and inte-
grated bus diagnostic.
Dimensions in mm 0° 45° 90°
A 64 61 66
B 34 53 40
C 15.8 15.8 15.8
To connect this EasyConn plug, please use the standard PROFIBUS
cable type A (EN50170). Starting with release 5 you also can use highly
flexible bus cable:
Lapp Kabel order no: 2170222, 2170822, 2170322.
W
ith the order no. 905-6AA00 VIPA offers the "EasyStrip" de-isolating
tool that makes the connection of the EasyConn much easier.
Dimensions in mm
The "EasyConn" bus connector is provided with a switch that is used to activate a termi-
nating resistor
.
EasyConn bus connector
Termination with "Easy-
Conn"
VIPA System MICRO
Option: Deployment PROFIBUS communication
PROFIBUS installation guidelines
HB400 | CPU | M13-CCF0000 | en | 16-47 175