EasyManua.ls Logo

YASKAWA VIPA System MICRO M13-CCF0000 - Page 215

YASKAWA VIPA System MICRO M13-CCF0000
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Event ID Description
0xE0CC Communication errors
ZInfo1 : Error code
1: Wrong priority
2: Buffer overflow
3: Telegram format error
4: Wrong SSL request (SSL ID not valid)
5: Wrong SSL request (SSL sub ID invalid)
6: Wrong SSL request (SSL-Index not valid)
7: Wrong value
8: Wrong return value
9: Wrong SAP
10: Wrong connection type
11: Wrong sequence number
12: Faulty block number in the telegram
13: Faulty block type in the telegram
14: Inactive function
15: Wrong size in the telegram
20: Error in writing on MMC
90: Faulty buffer size
98: Unknown error
99: Internal error
0xE0CD Error at DP-V1 job management
ZInfo1 : Not relevant to the user
ZInfo2 : Not relevant to the user
ZInfo3 : Not relevant to the user
DatID : Not relevant to the user
0xE0CE Error: Timeout at sending of the i-slave diagnostics
0xE100 Memory card access error
0xE101 Memory card error file system
0xE102 Memory card error FAT
0xE104 Memory card error at saving
ZInfo3 : Not relevant to the user
0xE200 Memory card writing finished (Copy Ram2Rom)
PK : Not relevant to the user
OB : Not relevant to the user
0xE210 Memory card reading finished (reload after overall reset)
ZInfo1 : Not relevant to the user
PK : Not relevant to the user
VIPA System MICRO
System specific event IDs
HB400 | CPU | M13-CCF0000 | en | 16-47 215