n Diagnostics interrupt DO power section supply
n Diagnostics interrupt DO short circuit/overload
The following parameters may be accessed by means of the properties dialog of the VIPA
CPU.
n Additional retentive memory
– Here enter the number of retentive memory bytes. With 0 the value
‘Retentive memory è Number of memory bytes starting with MB0’ is set, which is
pre-set at the parameters of the Siemens CPU.
– Range of values: 0 (default) ... 8192
n Additional retentive timer
– Enter the number of S7 timers. With 0 the value ‘Retentive memory
è Number S7 timers starting with T0’ is set, which is pre-set at the parameters of
the Siemens CPU.
– Range of values: 0 (default) ... 512
n Additional retentive counter
– Enter the number of S7 counter. With 0 the value ‘Retentive memory
è Number S7 counters starting with C0’ is set, which is pre-set at the parameters
of the Siemens CPU.
– Range of values: 0 (default) ... 512
n Diagnostics interrupt (default: deactivated)
– Diagnostics interrupt DI power section supply
Error: 3L+ (DC 24V DI power section supply) missing respectively <19V
– Diagnostics interrupt DO power section supply
Error: 4L+ (DC 24V DO power section supply) missing respectively <19V
– Diagnostics interrupt DO short circuit/overload
Error: Short circuit or overload of an digital output respectively current exceeds
0.5A.
VIPA specific parameters
VIPA System MICRO
Deployment CPU M13-CCF0000
Setting VIPA specific CPU parameters
HB400 | CPU | M13-CCF0000 | en | 16-47 67