172
Protective
Operation
Output is
turned OFF
and motor
coasts to a
stop.
OH (Heatsink overheat)
Temperature increased be-
cause of Inverter overload op-
eration or intake air
temperature rise.
• Excessive load
Improper V/f pattern set-
ting
• Insufficient acceleration
time if the fault occurs
during acceleration
• Intake air temperature
exceeding 50°C
Cooling fan stops.
Cooling fan deteriorates
its cooling capability or
stops.
Fin is clogged.
There is a thermal source
around the Inverter
Check the following:
• Load size
V/f pattern setting (con-
stants n011 to n017)
• Intake air temperature.
Cooling fan is turning
while the Inverter is run-
ning.
Any foreign matters
adhere to the fan and that
they do not interrupt the
rotation.
Fan is mounted properly.
There is not a thermal
source around the
Inverter.
RH (Externally-mount-
ing-type braking resistor
overheat) *
Protection of externally-
mounting type
braking resistor operated.
• Insufficient deceleration
time
Excessive motor regener-
ative energy
• Increase deceleration
time
Reduce regenerative load
* Indicates that an Inverter of 5.5 kW and 7.5 kW (200-V and 400-V classes) is attached.
Fault Display Inverter
Status
Description Causes and Corrective
Actions