9. Specifications
183
* 1. Based on a standard 4-pole motor for max. applicable motor output.
* 2. Shows deceleration torque for uncoupled motor decelerating from 60 Hz
with the shortest possible deceleration time.
* 3. The operation level becomes approx. 50% of Inverter rated output current
in case of Inverters of 5.5 kW or 7.5 kW.
* 4. The ground fault here is one which occurs in the motor wiring while the
motor is running. A ground fault may not be detected in the following
cases.
• A ground fault with low resistance which occurs in motor cables or ter-
minals.
• A ground fault occurs when the power is turned ON.
* 5. Minimum permissible load: 5 VDC, 10 mA (as reference value)
* 6. 0P1 to 3P7 are of IP20. Be sure to remove the top and bottom covers
when Inverter 5P5 or 7P5 of open chassis mounting type is used.
* 7. NEMA 1 of 0P1 to 3P7 is optional, while NEMA 1 of 5P5 and 7P5 is pro-
vided as standard.
* 8. Temperature during shipping (for short period).
Ambient Temperature Open chassis (IP20, IP00): 10 to 50°C
Enclosed wall-mounted NEMA 1 (TYPE 1): 10 to 40°C (not frozen)
Humidity 95% or less (non-condensing)
Storage Temperature
*8
20 to 60°C
Location Indoor (free from corrosive gases or dust)
Elevation 1,000 m or less
Vibration
Up to 9.8 m/s
2
(1G) at 10 to less than 20 Hz,
up to 2 m/s
2
(0.2G) at 20 to 50 Hz
Voltage Class 200 V single-/3-phase
Model
CIMR-
V7T

3-phase 20P1 20P2 20P4 20P7 21P5 22P2 23P7 25P5 27P5
Single-phase B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B3P7 - -
Environmental Conditions

Table of Contents