9. Specifications
205
Third Functions (Constants n080 to n119)
No. Register
No. for
Trans-
mission
Name Setting Range Setting Unit Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page
080 0150 Carrier Frequency Selection 1 to 4, 7 to 9 - (Note 4) No 83
081 0151 Momentary Power Loss
Ridethrough Method
0 to 2
(Note 10)
-0No72
082 0152 Automatic Retry Attempts 0 to 10 times - 0 No 77
083 0153 Jump Frequency 1 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz No 76
084 0154 Jump Frequency 2 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz No 76
085 0155 Jump Frequency 3 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz No 76
086 0156 Jump Frequency Range 0.00 to
25.50 Hz
0.01 Hz 0.00
Hz
No 76
087 0157 Cumulative operation time
function selection
(Note 9)
0, 1 - 0 No -
088 0158 Cumulative operation time
(Note 9)
0 to 6550 1 = 10H 0H No -
089 0159 DC Injection Braking Current 0 to 100% 1% 50% No 78
090 015A DC Injection Braking Time at
Stop
0.0 to 25.5 s 0.1 s 0.5 s No 88
091 015B DC Injection Braking Time at
Startup
0.0 to 25.5 s 0.1 s 0.0 s No 78
092 015C Stall Prevention During Decel-
eration
0, 1 - 0 No 105
093 015D Stall Prevention Level During
Acceleration
30% to 200% 1% 170% No 102
094 015E Stall Prevention Level During
Running
30% to 200% 1% 160% No 105
095 015F Frequency Detection Level 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz No 75

Table of Contents