9. Specifications
209
146 0192 Search Operation Voltage
Step at 5%
0.1% to 10.0% 0.1% 0.2% No 127
149 0195 Pulse Train Input Scaling 100 to 3300 1 = 10 Hz 2500
(25 kHz)
No 101
150 0196 Pulse Monitor Output Fre-
quency Selection
0, 1, 6, 12, 24,
36, 40 to 45
-0No81
151 0197 MEMOBUS Timeover Detec-
tion
0 to 4 - 0 No 111
152 0198 MEMOBUS Frequency Refer-
ence and Frequency Monitor
Unit
0 to 3 - 0 No 111
153 0199 MEMOBUS Slave Address 0 to 32 - 0 No 112
154 019A MEMOBUS BPS Selection 0 to 3 - 2 No 112
155 019B MEMOBUS Parity Selection 0 to 2 - 0 No 112
156 019C Transmission Waiting Time 10 to 65 ms 1 ms 10 ms No 112
157 019D RTS Control 0, 1 - 0 No 112
158 019E Motor Code (Energy-saving
Control)
0 to 70 - (Note 7) No 125
159 019F Upper Voltage Limit for Ener-
gy-saving Control at 60 Hz
0% to 120% 1% 120% No 126
160 01A0 Upper Voltage Limit for Ener-
gy-saving Control at 6 Hz
0% to 25% 1% 16% No 126
161 01A1 Search Operation Power De-
tection Hold Width
0% to 100% 1% 10% No 128
162 01A2 Time Constant of Power De-
tection
Filter
0 to 255 1 = 4 ms 5 (20 ms) No 128
163 01A3 PID Output Gain 0.0 to 25.0 0.1 1.0 No 134
164 01A4 PID Feedback Value Selection 0 to 5 - 0 No 132
165 01A5 Externally-mounting type brak-
ing resistor overheat protec-
tion selection
(Note 8)
0, 1 - 0 No -
166 01A6 Input Open-phase Detection
Level
0% to 100% 1% 0% No 152
167 01A7 Input Open-phase Detection
Time
0 to 255 s 1 s 0 s No 152
168 01A8 Output Open-phase Detection
Level
0% to 100% 1% 0% No 152
No. Register
No. for
Trans-
mission
Name Setting Range Setting Unit Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page