SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
3
PROGRAMMABLE
BUTTON ACCESS LEVEL DESCRIPTION
Print VIEW
Use this key to generate a hard-copy report of the present system status. This
provides a snapshot of the primary operating conditions at the time the key is
pressed. The History page provides enhanced reporting capability. (See HISTO-
RY Screen.) This option will not be present if the chiller is presently congured to
print History, New Data, which continuously logs.
Clear Fault VIEW
When safety conditions have been detected, the chiller is shutdown, and the
main status display of the chiller will display a message indicating the cause of
the shutdown. Using this key, the fault and message can be cleared once the
condition has been removed. The key only shows when the condition can be
cleared. If the chiller has a standing Local or Remote run command, it will start
when the key is pressed.
Warning Reset OPERATOR
Use of this key acknowledges a warning condition and resets the message
display associated with it.
Start OPERATOR
This key is only available when the chiller does not have a local run request.
Pressing this key allows selection of enter to run or cancel to abort to stopped.
Enter causes the chiller to start if control source is LOCAL, or permits run if the
Run/Stop source is any remote mode.
Soft Stop OPERATOR
This key is displayed whenever the chiller is running. It shows in place of the
start key. Pressing this key allows selection of enter to stop or cancel to remain
running. Enter causes the chiller to perform a soft shutdown and disables the
remote run permissive. This key should always be used to stop the chiller un-
less an emergency situation exists, in which case the Safety Stop button can be
used.
NAVIGATION
NAVIGATION
BUTTON DESCRIPTION
System Jumps to the System Screen.
Evaporator Navigates to the Evaporator Screen.
Condenser Navigates to the Condenser Screen.
Compressor
Navigates to the Compressor Screen for a detailed view of all the compressor
parameters.
Capacity Control
Navigates to the Capacity Control Screen for a detailed view of all the param-
eters associated with capacity control
Motor
Navigates to the VSD Screen to view VSD parameters. This screen allows pro-
gramming of the Current Limit and the Pulldown Demand Limit values.
Setpoints
This screen provides a single location to program the most common system
setpoints. It is also the gateway to many of the general system setup parameters
such as Date/Time, Display Units, Scheduling, Printer Setup, etc.
History
This screen provides access to a snapshot of system data at each of the last 50
shutdown conditions, and provides for trending operating parameters.