JOHNSON CONTROLS
48
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
PROGRAMMABLE
PROGRAMMABLE
BUTTON ACCESS LEVEL DESCRIPTION
Shutdown
(Enabled/
Disabled)
Operator
Allows the user to select whether the chiller will shutdown or continue to run
when an Excess Surge situation has been detected.
Extended Run
(Enabled/
Disabled)
Operator
Allows the user to select whether the chiller will shut-down or continue to run
when an Excess Surge situation has been detected.
Count Window Operator
Allows the user to dene the period of time (1 to 5 minutes; default 5; default 3
in which the number of surge events (SURGE WINDOW COUNT) are compared
to the maximum allowed (COUNT LIMIT), for the purpose of detecting an excess
surge situation
Count Limit Operator
Allows the user to dene the maximum number of surge events (4 to 20; default
4; default 15 that can occur within a dened period of time before an Excess
Surge situation is detected. If the SURGE WINDOW COUNT exceeds the
COUNT LIMIT, an Excess Surge situation has occurred.
When an Excess Surge situation is detected, and the SHUTDOWN setpoint is
Enabled, the chiller will perform a safety shutdown and display SURGE PRO-
TECTION – EXCESS SURGE.
NAVIGATION
NAVIGATION
BUTTON DESCRIPTION
Home Causes an instant return to the Home Screen.
Condenser Causes an instant return to the Compressor Screen.