JOHNSON CONTROLS
85
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
3
PROGRAMMABLE
PROGRAMMABLE
BUTTON ACCESS LEVEL DESCRIPTION
Primary Trigger Operator
Selects the rst parameter to be evaluated. Selection is made from the Slot
Numbers listing on the Trend Common Slots Screen or the Master Slot Numbers
List in this manual. Setting this slot number to zero disables the Primary Trigger.
Primary
Operator
Operator
Selects the comparator for the Primary Trigger’s relationship to the Primary Test.
If the Primary Trigger is an analog value, selections are: <, <=, =, =>, >. If the
Primary Trigger is a digital event, selections are: Equal To, Not Equal To.
Primary Test Operator
Selects the value or condition that the Primary Trigger is compared to. Selection
ranges from the Primary Trigger minimum value to the Primary Trigger maximum
value.
Trigger Action Operator
Selects whether the trend data collection will Start or Stop when the Trigger
comparisons are true. If set to Start, data collection will stop after one screen of
data is collected
Trigger Delay Operator
Allows the data collection start or stop to be delayed after the Triggers evaluate
as true. The delay is selectable from 1 to 864000 seconds (10 days). Display is
in days, hours, minutes and seconds. The delay timer begins when the triggers
evaluate as true. If the Trigger Action is set to Start, data collection will begin
after the triggers evaluate as true and the delay timer has elapsed. If the Trigger
Action is set to Stop, data collection will stop after the Triggers evaluate as true
and the delay timer has elapsed.
Primary to
Secondary
Operator
Operator
Selects whether the Primary Trigger, Secondary Trigger or both have to be true
in order to start or stop data collection. Selections are AND, OR, XOR and None.
If NONE is selected, the Secondary Trigger is disabled.
Data collection will start/stop (as selected with Trigger Action):
• If AND is selected: Both Primary AND Secondary are true
• If OR is selected: Either Primary OR Secondary (or both) are true
• If XOR is selected: Either Primary OR Secondary (but not both) are true
Secondary
Trigger
Operator
Selects the second parameter to be evaluated. Selection is made from the
Slot Numbers listing on the Trend Common Slots Screen or the Master
Slot Numbers List in this manual. Setting this slot number to zero disables
the Secondary Trigger.
Secondary
Operator
Operator
Selects the comparator for the Secondary Trigger’s relationship to the
Secondary Test. If the Secondary trigger is an Analog value, selections
are: <, <=, =, =>, >. If the Secondary Trigger is a digital event, selections
are: Equal To, Not Equal To.
Secondary Test Operator
Selects the value or condition that the Secondary Trigger is compared to.
Selection ranges from the Secondary Trigger minimum to the Secondary
Trigger maximum.
NAVIGATION
NAVIGATION
BUTTON DESCRIPTION
Home Causes a return to the Home Screen.
Trend Setup Causes an instant return to the Trend Setup Screen.