EasyManua.ls Logo

Zapi ACE0 2mC - Page 110

Zapi ACE0 2mC
155 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page – 110/155 AF6ZP0CA – COMBIAC0 & ACE0 2uC – User Manual
current from the capacitors-charging circuit, thus preventing the caps
from charging well. Check if a lamp or a dc/dc converter or an auxiliary
load is placed in parallel to the capacitor bank.
- The charging resistance or PTC may be broken. Insert a power
resistance across line-contactor power terminals; if the alarm disappears,
it means that the charging resistance is damaged.
- The charging circuit has a failure or there is a problem in the power
section. Replace the controller.
CHECK UP NEEDED (MDI/LED code = 0)
Cause:
This is a warning to point out that it is time for the programmed maintenance.
Troubleshooting
:
Turn on the CHECK UP DONE option after that the maintenance service.
COIL SHOR. EB (MDI/LED code = 76)
Cause
This alarm occurs when an overload of the EB driver (output NEB A4)
occurs.
Troubleshooting
- Check the connections between the controller outputs and the loads.
- Collect information about characteristics of the coil connected to the
driver and ask for assistance to a Zapi technician in order to verify that
the maximum current that can be supplied by the hardware is not
exceeded.
- In case no failures/problems have been found, the problem is in the
controller, which has to be replaced.
COIL SHOR. EVAUX (MDI/LED code = 21)
Cause:
This alarm occurs when an overload of the EV drivers occurs.
Troubleshooting
:
- Check the connections between the controller outputs and the loads.
- Collect information about characteristics of the coils connected to the
drivers and ask for assistance to a Zapi technician in order to verify that
the maximum current that can be supplied by the hardware is not
exceeded.
In case no failures/problems have been found, the problem is in the
controller, which has to be replaced.
COIL SHOR. MC (MDI/LED code = 76)
Cause
This alarm occurs when an overload of the MC driver (output NMC A12)
occurs.
Troubleshooting
- Check the connections between the controller outputs and the loads.
- Collect information about characteristics of the coil connected to the
driver and ask for assistance to a Zapi technician in order to verify that
the maximum current that can be supplied by the hardware is not
exceeded.

Table of Contents

Related product manuals