How to fix MODBUS connection issues with my ZIEHL-ABEGG Fan motor?
- KKaren AdamsAug 22, 2025
If the MODBUS connection to the ZIEHL-ABEGG Fan motor is not possible, it could be due to: * Incorrect connection: data lines A and B mixed up. Check the wiring. * Wrong communication parameters. Verify the communication parameters. * Wrong slave address set. Carry out automatic addressing again. Carry out the MODBUS recovery function after consulting ZIEHLABEGG support.