8.4 Menu group Info
Info
Speed
Motor speed
Motor current
Display of internal motor current (metering precision approx. +/-10 %)
Brake control
Display of modulation 0...100 % (metering precision approx. +/- 10 %)
Motor input power
Display of input power (metering precision approx. +/-10 %)
8.5 Menu group Controller Setup
Controller Setup
Information
The following factory settings specifications are not binding, these values can differ depending on the
software version and customer-specific pre-setting.
8.5.1 Controlmode
Type of device modulation.
0
Factory setting
Control by external signal (0 - 10 V / PWM) at the input “E1”.
Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible (
IO Setup).
1
no function
2
no function
3
no function
4
constant speed “Set Internal1”.
Switching to fixed speed “Default Internal2” or “Default Internal3” via digital input
possible (
IO Setup).
5
Fixed speed “Default Internal2” (without switching possibility to other default).
6
Fixed speed “Default Internal3” (without switching possibility to other default).
Assembly instructions ECblue Programming by hand held terminal A-G-247NW
L-BAL-F055D-GB 2021/51 Index 006 Part.-No.
31/56