Examples
Do not loosen the safety screws from the housing!
Connection
Diagram
Lead
Color
on field side
according to
local / national
requirements
e.g.
NEC / NFPA
BU
BN
WH
WH
GNYE
N
L1
RC
RC
PE
PWM
BK Data
+
0
-10V /
YE
Digital In
GN
BU
RD
WH
OC Out
Data -
BN
A
E1
D1
GND
10V
A1
B
GN or GNYE
WH or GR
BU or RD
00700859
12.01.2015
The bands around the cables show national colour codes which may be
available on the eld side.
For line and relay: hose cable 5 x 1.0 mm
2
(18 AWG) comparable LiYY-JB
BN
BU
GNYE
WH
WH
length approx. 0.6 m *
brown L1
Lineblue N
green-yellow PE
white 11
Relay
white 14 K1
For control: hose cable 7 x 0.34 mm
2
(22 AWG) comparable LiYY-OB
BK
WH
BN
BU
YE
GN
RD
length approx. 0.6 m *
brown B (D-) MODBUS (RS-485)
black A (D+) MODBUS (RS-485)
white A1 OC Out Status (Tacho)
green D1 Digital In 1
yellow E1 Analog In 1
blue GND
red 10V
DC Out
* The lead length can vary according to the version.
5.4 VVersion with connection via M12 connector
Information
When assembling the connecting cables with M12 connectors, refer to the connection diagrams
with pin assignment supplied and the connection diagram contained in the instructions.
The type, count, coding and pin assignment of the plug connections may vary depending on the
version.
Tighten the ring nut on the side of the connecting cable hand tight to lock the plug connection.
It is not necessary to remove the lid for the connection.
Assembly instructions ECblue Electrical installation
L-BAL-F055D-GB 2021/51 Index 006 Part.-No.
19/56