8.6.5 Networking via MODBUS
It is possible to network several devices with each other. The device uses the MODBUS-RTU as the
protocol for the RS-485 interface.
Bus Address
The device address is factory set to the highest available MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
UART Baudrate
Setting transfer rate
Valid values: 4800, 9600, 19200, 38400
Factory setting: 19200
Illegal value: 115200
UART Mode
Setting transfer format
Valid values: 8O1, 8N1, 8E1
Factory setting: 8E1
Information
If it is attempted to change the baud rate to an impermissible value (e.g. 115200), the following
exception code will be sent back:
|
Exception Code 3: Illegal Data Value
|
.
8.7 Menu group Motor Setup
Motor Setup
Rated speed
MotorRatedCurr. * The following controller presettings are dependent on the
respective motor design and are only shown for information.
Rated speed
MotorRatedCurr.
Rotat. Direction
Value motorheating
Rampup time
Rampdown time
Rotat. Direction
Value motorheating
Suppression1
Assembly instructions ECblue Programming by hand held terminal A-G-247NW
L-BAL-F055D-GB 2021/51 Index 006 Part.-No.