8.6.5 Networking via MODBUS
It is possible to network several devices with each other. The device uses the MODBUS-RTU as the
protocol for the RS-485 interface.
Bus Address
The device address is factory set to the highest available MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
UART Baudrate
Setting transfer rate
Valid values: 4800, 9600, 19200, 38400
Factory setting: 19200
Illegal value: 115200
UART Mode
Setting transfer format
Valid values: 8O1, 8N1, 8E1
Factory setting: 8E1
Information
If it is attempted to change the baud rate to an impermissible value (e.g. 115200), the following
exception code will be sent back:
|
Exception Code 3: Illegal Data Value
|
.
8.7 Menu group “Motor Setup”
Motor Setup
Rated speed
MotorRatedCurr. * The following controller presettings are dependent on the
respective motor design and are only shown for information.
•
Rated speed
•
MotorRatedCurr.
•
Rotat. Direction
•
Value motorheating
Rampup time
Rampdown time
Rotat. Direction
Value motorheating
Suppression1
Assembly instructions ECblue Programming by hand held terminal A-G-247NW
L-BAL-F055D-GB 2021/51 Index 006 Part.-No.
37/56