10.2 Cleaning
Danger due to electric current
Voltage supply for motor must be interrupted and secured against restoration!
Clean the fans`s ow area.
Attention!
Do not use any aggressive, paint solvent cleaning agents when cleaning.
Make sure that no water gets inside the motor and the electronics (e.g. by direct contact with seals
or motor openings), observe protection class (IP).
The drain holes (if available) corresponding to the installation position must be checked for free
passage.
In case of improper cleaning work, no warranty is assumed regarding corrosion formation / paint
adhesion for unpainted / painted fans.
To avoid accumulation of moisture in the motor, the fan must be operated for at least 1 hour at 80%
to 100 % of the maximum speed before the cleaning process!
After the cleaning process, the fan must be operated for at least 2 hours at 80 to 100 % of the
maximum speed for drying purposes!