Harmonics current Active power factor adjustment for sinusoidal input current (PFC = Power - Factor
- controller), harmonic current in accordance with EN 61000-3-2 are guaranteed.
Contact rating of the internal relay K1 AC 250 V 2 A
Max. leakage current according to the de-
ned networks of EN 60990
< 3.5 mA
dB(A) values see product catalogue
Protection class of motor according to
EN 60529
IP54
* Regarding the mains connection, these devices are to be classied as category C2 devices according to the relevant
DIN EN 61800-3. The increased requirements placed on electrical interference > 2 kHz for category C1 devices are
complied with in addition.
** Max. line fuse on site (line protection fuse) according to EN 60204-1 Classication VDE0113 Part 1 (see also Assembly
instructions / Electrical installation / Voltage supply / Line protection fuse).
For motors with the corresponding quality mark (see rating plate)
Authorization: FILE No. E347018 UL 1004-1, UL 1004-3, UL 1004-7;
CAN/CSA C22.2 No.100, CAN/CSA C22.2 No.77
Electronically Protected Motors
For motors with the corresponding quality mark (see rating plate)
Rated voltage 200 - 240 V, 50/60 Hz
Zulassung REG.-Nr. E418
Certicate number 40039441
DIN EN 60335-1 (VDE 0700-1):2020-08; EN 60335-
1:2012+AC+A11+A13+A1+A2+A14:2019
EN 60335-1:2012/A15:2021
Einbaumotor (Built-in-motor)
Assembly instructions ECblue Enclosure
L-BAL-F055D-GB 2021/51 Index 006 Part.-No.
49/56