VCCX2 Controller Technical Guide
Return Air Temperature Sensor
G051240 (6 inch) or G051250 (12 inch) Return Air Temperature
Sensor must be wired as shown for proper operation. The Return
Air Temperature Sensor is a 10K Type III thermistor sensor. The
Return Air Temperature Sensor should be mounted in the return
air duct. If the system has a Zoning Bypass Damper installed, be
sure the return air sensor is located upstream of the bypass duct
connection. See Figure 13, this page for details.