Communication with M-Bus
2CMC48001M0201 235 A43/A44
Revision: C User Manual
Status information The manufacturer specific coding of the status information is used to indicate
the following:
Date/time was changed during the interval
Data overflow in interval
Intervals are too long or too short
Power outage occurred during the interval
If one or several of these status events occur during an interval, the extra VIFE’s FF
FE 0x are sent out, where x is a bit 4-0 and have the following meaning if set:
Bit 4
Date/time was changed during the interval
Bit 3
Data overflow in interval
Bit 2
Power outage occurred during interval
Bit 1
Short interval
Bit 0
Long interval
10.4.1.1 Examples of Readouts of Load Profile Data
Introduction In the following are a number of practical examples of load profile readouts. All
data is hexadecimal and comments are preceded by a semicolon.