78 ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
9083 External fault 3
(Editable message text)
Programmable fault: 31.05
External event 3 source
31.06 External event 3
type
Fault in external
device 3.
Check the external device.
Check setting of parameter 31.05
External event 3 source.
9084 External fault 4
(Editable message text)
Programmable fault: 31.07
External event 4 source
31.08 External event 4
type
Fault in external
device 4.
Check the external device.
Check setting of parameter 31.07
External event 4 source.
9085 External fault 5
(Editable message text)
Programmable fault: 31.09
External event 5 source
31.10 External event 5
type
Fault in external
device 5.
Check the external device.
Check setting of parameter 31.09
External event 5 source.
FA81 Safe torque off 1 Safe torque off function
is active, ie. STO circuit
1 is broken.
Check safety circuit connections. For
more information, see chapter The
Safe torque off function in the
Hardware manual of the drive and
parameter 31.22 STO indication run/
stop.
Check the value of parameter 95.04
Control board supply.
FA82 Safe torque off 2 Safe torque off function
is active, ie. STO circuit
2 is broken.
FF61 ID run Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group 99 Motor data.
Check that no external control system
is connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not
locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
0001 Maximum current limit
too low.
Check settings of parameters 99.06
Motor nominal current and 30.17
Maximum current. Make sure that
30.17 > 99.06.
Check that the drive is dimensioned
correctly according to the motor.
Code
(hex)
Fault / Aux. code Cause What to do