ACQ550-U1 User’s Manual 107
Parameters
1605 USER PAR SET CHG
Defines control for changing the user parameter set.
See parameter 9902
APPLIC MACRO.
The drive must be stopped to change User Parameter Sets.
During a change, the drive will not start.
Note: Always save the User Parameter Set after changing any parameter settings, or performing a motor
identification.
Whenever the power is cycled, or parameter 9902
APPLIC MACRO is changed, the drive loads the last settings
saved. Any unsaved changes to a user parameter set are lost.
Note: The value of this parameter (1605) is not included in the User Parameter Sets, and it does not change if User
Parameter Sets change.
Note: You can use a relay output to supervise the selection of User Parameter Set 2.
See parameter 1401.
0 =
NOT SEL – Defines the control panel (using parameter 9902) as the only control for changing User Parameter
Sets.
1 =
DI1 – Defines digital input DI1 as a control for changing User Parameter Sets.
The drive loads User Parameter Set 1 on the falling edge of the digital input.
The drive loads User Parameter Set 2 on the rising edge of the digital input.
The User Parameter Set changes only when the drive is stopped.
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as a control for changing User Parameter Sets.
•See
DI1 above.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as a control for changing User Parameter Sets.
The drive loads User Parameter Set 1 on the rising edge of the digital input.
The drive loads User Parameter Set 2 on the falling edge of the digital input.
The User Parameter Set changes only when the drive is stopped.
-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as a control for changing User Parameter Sets.
•See
DI1(INV) above.
1607 PARAM SAVE
Saves all altered parameters to permanent memory.
Parameters altered through a fieldbus are not automatically saved to permanent memory. To save, you must use
this parameter.
If 1602
PARAMETER LOCK = 2 (NOT SAVED), parameters altered from the control panel are not saved. To save, you
must use this parameter.
If 1602
PARAMETER LOCK = 1 (OPEN), parameters altered from the control panel are stored immediately to
permanent memory.
0 = DONE – Value changes automatically when all parameters are saved.
1 =
SAVE… – Saves altered parameters to permanent memory.