94 ACQ550-U1 User’s Manual
Parameters
Group 11: REFERENCE SELECT
This group defines:
how the drive selects between command sources
characteristics and sources for
REF1 and REF2.
Code Description
1101 KEYPAD REF SEL
Selects the reference controlled in local control mode.
1 = REF1(Hz/rpm) – Reference type depends on parameter 9904 MOTOR CTRL MODE.
Speed reference (rpm) if 9904 = 1 or 2 (
VECTOR:sPEED).
Frequency reference (Hz) if 9904 = 3 (
SCALAR:FREQ).
2 =
REF2(%)
1102 EXT1/EXT2 SEL
Defines the source for selecting between the two external control locations
EXT1 or EXT2. Thus, defines the source for
Start/Stop/Direction commands and reference signals.
0 = EXT1 – Selects external control location 1 (EXT1).
See parameter 1001
EXT1 COMMANDS for EXT1’s Start/Stop/Dir definitions.
See parameter 1103
REF1 SELECT for EXT1’s reference definitions.
1 =
DI1 – Assigns control to EXT1 or EXT2 based on the state of DI1 (DI1 activated = EXT2; DI1 de-activated = EXT1).
2…6 =
DI2…DI6 – Assigns control to EXT1 or EXT2 based on the state of the selected digital input. See DI1 above.
7 =
EXT2 – Selects external control location 2 (EXT2).
See parameter 1002
EXT2 COMMANDS for EXT2’s Start/Stop/Dir definitions.
See parameter 1106
REF2 SELECT for EXT2’s reference definitions.
8 =
COMM – Assigns control of the drive via external control location EXT1 or EXT2 based on the fieldbus control word.
Bit 5 of the Command Word 1 (parameter 0301) defines the active external control location (
EXT1 or EXT2).
See Fieldbus user’s manual for detailed instructions.
9 = TIMED FUNC 1 – Assigns control to EXT1 or EXT2 based on the state of the Timed Function (Timed Function
activated =
EXT2; Timed Function de-activated = EXT1). See Group 36: TIMED FUNCTIONS.
10…12 =
TIMED FUNC 2…4 – Assigns control to EXT1 or EXT2 based on the state of the Timed Function. See TIMED
FUNC 1 above.
-1 =
DI1(INV) – Assigns control to EXT1 or EXT2 based on the state of DI1 (DI1 activated = EXT1; DI1 de-activated =
EXT2).
-2…-6 =
DI2(INV)…DI6(INV) – Assigns control to EXT1 or EXT2 based on the state of the selected digital input. See
DI1(INV) above.
1103 REF1 SELECT
Selects the signal source for external reference
REF1.
0 =
KEYPAD – Defines the control panel as the reference
source.
1 = AI1 – Defines analog input 1 (AI1) as the reference
source.
2 =
AI2 – Defines analog input 2 (AI2) as the reference
source.
3 =
AI1/JOYST – Defines analog input 1 (AI1), configured for
joystick operation, as the reference source.
The minimum input signal runs the drive at the maximum
reference in the reverse direction. Define the minimum
using parameter 1104.
The maximum input signal runs the drive at maximum
reference in the forward direction. Define the maximum
using parameter 1105.
Requires parameter 1003 = 3 (
REQUEST).
WARNING! Because the low end of the reference
range commands full reverse operation, do not use 0 V as the lower end of the reference range. Doing so
means that if the control signal is lost (which is a 0 V input) the result is full reverse operation. Instead, use
the following set-up so that loss of the analog input triggers a fault, stopping the drive:
Set parameter 1301
MINIMUM AI1 (1304 MINIMUM AI2) at 20% (2 V or 4 mA).
Set parameter 3021
AI1 FAULT LIMIT to a value 5% or higher.
Set parameter 3001
AI<MIN FUNCTION to 1 (FAULT).
4 =
AI2/JOYST – Defines analog input 2 (AI2), configured for joystick operation, as the reference source.
See above (
AI1/JOYST) description.
+2%-2%
10 V /
Hysteresis 4% of full scale
EXT REF 1 MIN
- EXT REF 1 MIN
- EXT REF 1 MAX
EXT
REF 1 MIN
EXT REF 1 MAX
- EXT REF 1 MIN
2V / 4mA
0V / 0mA
20 mA