150 ACQ550-U1 User’s Manual
Parameters
4016 ACT1 INPUT
Defines the source for actual value 1 (
ACT1). See also parameter 4018 ACT1 MINIMUM.
1 =
AI1 – Uses analog input 1 for ACT1.
2 =
AI2 – Uses analog input 2 for ACT1.
3 =
CURRENT – Uses current for ACT1.
4 =
TORQUE – Uses torque for ACT1.
5 =
POWER – Uses power for ACT1.
6 =
COMM ACT 1 – Uses value of signal 0158 PID COMM VALUE 1 for ACT1.
7 =
COMM ACT 2 – Uses value of signal 0159 PID COMM VALUE 2 for ACT1.
4017 ACT2 INPUT
Defines the source for actual value 2 (
ACT2). See also parameter 4020 ACT2 MINIMUM.
1 =
AI1 – Uses analog input 1 for ACT2.
2 =
AI2 – Uses analog input 2 for ACT2.
3 =
CURRENT – Uses current for ACT2.
4 =
TORQUE – Uses torque for ACT2.
5 =
POWER – Uses power for ACT2.
6 =
COMM ACT 1 – Uses value of signal 0158 PID COMM VALUE 1 for ACT2.
7 =
COMM ACT 2 – Uses value of signal 0159 PID COMM VALUE 2 for ACT2.
4018 ACT1 MINIMUM
Sets the minimum value for
ACT1.
• Scales the source signal used as the actual value
ACT1 (defined
by parameter 4016
ACT1 INPUT). For parameter 4016 values
6(
COMM ACT 1) and 7 (COMM ACT 2) scaling is not done.
• See the figure: A= Normal; B = Inversion (
ACT1 MINIMUM > ACT1
MAXIMUM)
4019 ACT1 MAXIMUM
Sets the maximum value for
ACT1.
• See 4018
ACT1 MINIMUM.
4020 ACT2 MINIMUM
Sets the minimum value for
ACT2.
• See 4018
ACT1 MINIMUM.
4021 ACT2 MAXIMUM
Sets the maximum value for
ACT2.
• See 4018
ACT1 MINIMUM.
4022 SLEEP SELECTION
Defines the control for the PID sleep function.
0 =
NOT SEL– Disables the PID sleep control function.
1 =
DI1 – Defines digital input DI1 as the control for the PID sleep function.
• Activating the digital input activates the sleep function.
• De-activating the digital input restores PID control.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for the PID sleep function.
•See
DI1 above.
7 =
INTERNAL – Defines the output rpm/frequency, process reference and process actual value as the control for the
PID sleep function. Refer to parameters 4025
WAKE-UP DEV and 4023 PID SLEEP LEVEL.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for the PID sleep function.
• De-activating the digital input activates the sleep function.
• Activating the digital input restores PID control.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for the PID sleep function.
•See
DI1(INV) above.
Code Description
Par 4016 Source Source min. Source max.
1 Analog input 1 1301 MINIMUM AI1 1302 MAXIMUM AI1
2 Analog input 2 1304
MINIMUM AI2 1305 MAXIMUM AI2
3 Current 0 2 · nominal current
4 Torque -2 · nominal torque 2 · nominal torque
5 Power -2 · nominal power 2 · nominal power
P 4019
P 4018
ACT1 (%)
A
B
Source signal
Source min. Source max.
P 4018
P 4019
ACT1 (%)
Source signal
Source min. Source max.