150 ACQ550-U1 User’s Manual
Parameters
4016 ACT1 INPUT
Defines the source for actual value 1 (
ACT1). See also parameter 4018 ACT1 MINIMUM.
1 =
AI1 – Uses analog input 1 for ACT1.
2 =
AI2 – Uses analog input 2 for ACT1.
3 =
CURRENT – Uses current for ACT1.
4 =
TORQUE – Uses torque for ACT1.
5 =
POWER – Uses power for ACT1.
6 =
COMM ACT 1 – Uses value of signal 0158 PID COMM VALUE 1 for ACT1.
7 =
COMM ACT 2 – Uses value of signal 0159 PID COMM VALUE 2 for ACT1.
4017 ACT2 INPUT
Defines the source for actual value 2 (
ACT2). See also parameter 4020 ACT2 MINIMUM.
1 =
AI1 – Uses analog input 1 for ACT2.
2 =
AI2 – Uses analog input 2 for ACT2.
3 =
CURRENT – Uses current for ACT2.
4 =
TORQUE – Uses torque for ACT2.
5 =
POWER – Uses power for ACT2.
6 =
COMM ACT 1 – Uses value of signal 0158 PID COMM VALUE 1 for ACT2.
7 =
COMM ACT 2 – Uses value of signal 0159 PID COMM VALUE 2 for ACT2.
4018 ACT1 MINIMUM
Sets the minimum value for
ACT1.
Scales the source signal used as the actual value
ACT1 (defined
by parameter 4016
ACT1 INPUT). For parameter 4016 values
6(
COMM ACT 1) and 7 (COMM ACT 2) scaling is not done.
See the figure: A= Normal; B = Inversion (
ACT1 MINIMUM > ACT1
MAXIMUM)
4019 ACT1 MAXIMUM
Sets the maximum value for
ACT1.
See 4018
ACT1 MINIMUM.
4020 ACT2 MINIMUM
Sets the minimum value for
ACT2.
See 4018
ACT1 MINIMUM.
4021 ACT2 MAXIMUM
Sets the maximum value for
ACT2.
See 4018
ACT1 MINIMUM.
4022 SLEEP SELECTION
Defines the control for the PID sleep function.
0 =
NOT SEL– Disables the PID sleep control function.
1 =
DI1 – Defines digital input DI1 as the control for the PID sleep function.
Activating the digital input activates the sleep function.
De-activating the digital input restores PID control.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for the PID sleep function.
•See
DI1 above.
7 =
INTERNAL – Defines the output rpm/frequency, process reference and process actual value as the control for the
PID sleep function. Refer to parameters 4025
WAKE-UP DEV and 4023 PID SLEEP LEVEL.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for the PID sleep function.
De-activating the digital input activates the sleep function.
Activating the digital input restores PID control.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for the PID sleep function.
•See
DI1(INV) above.
Code Description
Par 4016 Source Source min. Source max.
1 Analog input 1 1301 MINIMUM AI1 1302 MAXIMUM AI1
2 Analog input 2 1304
MINIMUM AI2 1305 MAXIMUM AI2
3 Current 0 2 · nominal current
4 Torque -2 · nominal torque 2 · nominal torque
5 Power -2 · nominal power 2 · nominal power
P 4019
P 4018
ACT1 (%)
A
B
Source signal
Source min. Source max.
P 4018
P 4019
ACT1 (%)
Source signal
Source min. Source max.