ACQ550-U1 User’s Manual 149
Parameters
Analog input reference correction
Parameter values 9, 10 and 14…17 use the formula in the following table.
Where:
C = Main reference value
( =
COMM for values 9, 10 and
=
AI1 for values 14…17)
B = Correcting reference
( =
AI1 for values 9, 10 and
=
AI2 for values 14…17).
Example:
The figure shows the reference source curves for
value settings 9, 10 and 14…17, where:
•C = 25%.
P 4012
SETPOINT MIN = 0.
P 4013
SETPOINT MAX = 0.
B varies along the horizontal axis.
4011 INTERNAL SETPNT
Sets a constant value used for the process reference.
Units and scale are defined by parameters 4006 and 4007.
4012 SETPOINT MIN
Sets the minimum value for the reference signal source.
See parameter 4010.
4013 SETPOINT MAX
Sets the maximum value for the reference signal source.
See parameter 4010.
4014 FBK SEL
Defines the PID controller feedback (actual signal).
You can define a combination of two actual values (ACT1 and ACT2) as the feedback signal.
Use parameter 4016 to define the source for actual value 1 (
ACT1).
Use parameter 4017 to define the source for actual value 2 (
ACT2).
1 =
ACT1 – Actual value 1 (ACT1) provides the feedback signal.
2 =
ACT1-ACT2 – ACT1 minus ACT2 provides the feedback signal.
3 =
ACT1+ACT2 – ACT1 plus ACT2 provides the feedback signal.
4 =
ACT1
*
ACT2 – ACT1 times ACT2 provides the feedback signal.
5 =
ACT1/ACT2 – ACT1 divided by ACT2 provides the feedback signal.
6 =
MIN(ACT1,2) – The smaller of ACT1 or ACT2 provides the feedback signal.
7 =
MAX(ACT1,2) – The greater of ACT1 or ACT2 provides the feedback signal.
8 = sqrt(
ACT1-2) – Square root of the value for ACT1 minus ACT2 provides the feedback signal.
9 = sq
A1+sqA2 – Square root of ACT1 plus the square root of ACT2 provides the feedback signal.
10 = sqrt(
ACT1) – Square root of ACT1 provides the feedback signal.
11 =
COMM FBK 1 – Signal 0158 PID COMM VALUE 1 provides the feedback signal.
12 =
COMM FBK 2 – Signal 0159 PID COMM VALUE 2 provides the feedback signal.
13 =
AVE(ACT1,2) – The average of ACT1 and ACT2 provides the feedback signal.
4015 FBK MULTIPLIER
Defines an extra multiplier for the PID feedback value FBK defined by parameter 4014.
Used mainly in applications where the flow is calculated from the pressure difference.
0.000 =
NOT SEL – The parameter has no effect (1.000 used as the multiplier).
-32.768…32.767 – Multiplier applied to the signal defined by parameter 4014
FBK SEL.
Example:
Code Description
Value setting Calculation of the AI reference
C + B C value + (B value - 50% of reference value)
C
*
B C value · (B value / 50% of reference value)
C - B (C value + 50% of reference value) - B value
C / B (C value · 50% of reference value) / B value
120
100
80
60
40
20
0
0
100%
9, 14 (+)
16 (-)
10, 15 (
*
)
17 (/)
B
FBK Multiplier A1 A2=