ACQ550-U1 User’s Manual 71
Parameters
Group 03: FB ACTUAL SIGNALS
0301
FB CMD WORD 1- - -
0302 FB CMD WORD 2- - -
0303
FB STS WORD 1- - -
0304
FB STS WORD 2- 1 -
0305 FAULT WORD 1- 1 -
0306
FAULT WORD 2- 1 -
0307 FAULT WORD 3- 1 -
0308
ALARM WORD 1- 1 -
0309
ALARM WORD 2- 1 -
Group 04: FAULT HISTORY
0401
LAST FAULT Fault codes (panel displays as text) 1 0
0402
FAULT TIME 1 Date dd.mm.yy / power-on time in days 1 day 0
0403
FAULT TIME 2 Time hh.mm.ss 2 s 0
0404
SPEED AT FLT -32768…+32767 1 rpm 0
0405
FREQ AT FLT -3276.8…+3276.7 0.1 Hz 0
0406 VOLTAGE AT FLT 0.0…6553.5 0.1 V 0
0407
CURRENT AT FLT 0.0…6553.5 0.1 A 0
0408
TORQUE AT FLT -3276.8…+3276.7 0.1% 0
0409 STATUS AT FLT 0000…FFFF hex 1 0
0410
DI 1-3 AT FLT 000…111 (0…7 decimal) 1 0
0411
DI 4-6 AT FLT 000…111 (0…7 decimal) 1 0
0412 PREVIOUS FAULT 1 As par. 0401 1 0
0413
PREVIOUS FAULT 2 As par. 0401 1 0
Group 10: START/STOP/DIR
1001 EXT1 COMMANDS 0…14 1 2 (DI1,2)
1002
EXT2 COMMANDS 0…14 1 0 (NOT SEL)
1003
DIRECTION 1=FORWARD, 2 = REVERSE,
3=
REQUEST
11=FORWARD
1004
JOGGING SEL -6…6 1 0 (NOT SEL)
Group 11: REFERENCE SELECT
1101
KEYPAD REF SEL 1=REF1(Hz/rpm), 2 = REF2(%) 1 1 [REF1(Hz/rpm)]
1102
EXT1/EXT2 SEL -6…12 1 0 (EXT1)
1103
REF1 SELECT 0…17, 20…21 1 1 (AI1)
1104
REF1 MIN 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
1105
REF1 MAX 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm -U1: 60.0 (62.0) Hz /
1800 rpm
1106
REF2 SELECT 0…17, 19…21 1 19 (PID1OUT)
1107
REF2 MIN 0.0…100.0% (0.0…600.0% for torque) 0.1% 0.0%
1108
REF2 MAX 0.0…100.0% (0.0…600.0% for torque) 0.1% 100.0%
Group 12: CONSTANT SPEEDS
1201
CONST SPEED SEL -14 …19 1 9 (DI3,4)
1202
CONST SPEED 1 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm -U1: 6.0 Hz / 360 rpm
1203
CONST SPEED 2 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm -U1: 12.0 Hz / 720 rpm
1204
CONST SPEED 3 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm -U1: 18.0 Hz / 1080 rpm
Code Name Range Resolution Default User S