96 ACQ550-U1 User’s Manual
Parameters
1104 REF1 MIN
Sets the minimum for external reference 1.
The minimum analog input signal (as a percent of the full
signal in volts or amperes) corresponds to
REF1 MIN in
Hz/rpm.
Parameter 1301
MINIMUM AI1 or 1304 MINIMUM AI2 sets
the minimum analog input signal.
These parameters (reference and analog min. and max.
settings) provide scale and offset adjustment for the
reference.
1105 REF1 MAX
Sets the maximum for external reference 1.
The maximum analog input signal (as a percent of full
the signal in volts or amperes) corresponds to
REF1 MAX
in Hz/rpm.
Parameter 1302
MAXIMUM AI1 or 1305 MAXIMUM AI2 sets
the maximum analog input signal.
1106 REF2 SELECT
Selects the signal source for external reference
REF2.
0…17 – Same as for parameter 1103
REF1 SELECT.
19 =
PID1OUT – The reference is taken from the PID1 output. See Group 40: PROCESS PID SET 1 and Group 41:
PROCESS PID SET 2.
20…21 – Same as for parameter 1103
REF1 SELECT.
1107 REF2 MIN
Sets the minimum for external reference 2.
The minimum analog input signal (in volts or amperes) corresponds to
REF2 MIN in %.
Parameter 1301
MINIMUM AI1 or 1304 MINIMUM AI2 sets the minimum analog input signal.
This parameter sets the minimum frequency reference.
The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque.
1108 REF2 MAX
Sets the maximum for external reference 2.
The maximum analog input signal (in volts or amperes) corresponds to
REF2 MAX in %.
Parameter 1302
MAXIMUM AI1 or 1305 MAXIMUM AI2 sets the maximum analog input signal.
This parameter sets the maximum frequency reference.
The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque.
Code Description
Ext ref
Analog
P 1105
P 1104
P 1301
P 1302
input signal
P 1301
P 1302
input signal
Analog
Ext ref
or 1304
or 1305
or 1304
or 1305
(
MAX)
(
MIN)
P 1105
P 1104
(
MAX)
(
MIN)
19=PID1 REF2
SELECT
LIMIT
MAX (1107, 1108)
MIN (1107, 1108)
PFC
If PFC is used
1…17
20…21