44 ACQ550-U1 User’s Manual
Control panel
W/WW control panel modes
The W/WW control panel has several different modes for configuring, operating and
diagnosing the drive. The modes are:
Standard Display Mode – Shows drive status information and operates the drive.
Parameters Mode – Edits parameter values individually.
Start-up Assistant Mode – Guides the start-up and configuration.
Changed Parameters Mode – Shows changed parameters.
Fault History Mode – Shows the drive fault history.
Drive Parameter Backup Mode – Stores or uploads the parameters.
Time & Date Mode – Sets the time and date for the drive.
I/O Settings Mode – Checks and edits the I/O settings.
Standard Display Mode
Use the Standard Display Mode to read information on the drive’s status and to
operate the drive. To reach the Standard Display Mode, press EXIT until the LCD
display shows status information as described below.
Status information
Top. The top line of the LCD display shows the basic status information of the drive.
•HAND Indicates that the drive control is local, that is, from the control panel.
•AUTO Indicates that the drive control is remote, such as the basic I/O (X1) or
fieldbus.
Indicates the drive and motor rotation status as follows:
Upper right shows the active reference.
Middle. Using parameter group 34, the middle of the LCD display can be configured
to display:
One to three parameter values The default display shows parameters 0102
(OUTPUT SPEED), 0104 (CURRENT) in amperes and 0105 (TORQUE) in
percentage.
Use parameters 3401, 3408, and 3415 to select the parameters (from Group
01) to display. Entering “parameter” 0100 results in no parameter displayed.
For example, if 3401 = 0100 and 3415 = 0100, then only the parameter
specified by 3408 appears in the Control Panel display.
You can also scale each parameter in the display, for example, to convert the
Control panel display Significance
Rotating arrow (clockwise or
counterclockwise)
Drive is running and at setpoint
Shaft direction is forward or reverse
Rotating dotted arrow blinking Drive is running but not at setpoint
Stationary dotted arrow Start command is present, but motor is not
running. E.g. start enable is missing.