ACQ550-U1 User’s Manual 67
Application macros
Macro default values for parameters
Parameter default values are listed in section Complete parameter list on page 69.
Changing from the default macro (ABB Standard), that is, editing the value of
parameter 9902, changes the parameter default values as defined in the following
tables.
Note: Configured for 60 Hz/NEMA compliance (ACQ550-U1).
ACQ550-U1
Parameter ABB 2-wire 3-wire Alternate
Motor
Potentio-
meter
Hand-auto PID Control PFC Control
9902
APPLIC MACRO 1=
ABB STANDARD
2=
3-WIRE
3=
ALTERNATE
4=
MOTOR POT
5=
HAND/AUTO
6=
PID CONTROL
7=
PFC CONTROL
9904 MOTOR CTRL MODE 3= SCALAR:
FREQ
1= VECTOR:
SPEED
1= VECTOR:
SPEED
1= VECTOR:
SPEED
1= VECTOR:
SPEED
1= VECTOR:
SPEED
3= SCALAR:
FREQ
1001 EXT1 COMMANDS 2= DI1,2 4= DI1P,2P,3 9= DI1F,2R 2= DI1,2 2= DI1,2 1= DI1 1= DI1
1002 EXT2 COMMANDS 0= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 7= DI6,5 6= DI6 6= DI6
1003 DIRECTION 3= REQUEST 3= REQUEST 3= REQUEST 3= REQUEST 3= REQUEST 1= FORWARD 1= FORWARD
1102 EXT1/EXT2 SEL 0= EXT10= EXT10= EXT10= EXT13= DI32= DI23= DI3
1103
REF1 SELECT 1= AI11= AI11= AI112=
DI3U,4D(NC)
1= AI11= AI11= AI1
1106 REF2 SELECT 2= AI22= AI22= AI22= AI22= AI219= PID1OUT 19 = PID1OUT
1201 CONST SPEED SEL 9= DI3,4 10 = DI4,5 9= DI3,4 5= DI5 0= NOT SEL 9= DI3,4 0= NOT SEL
1304 MINIMUM AI2 0.0% 0.0% 0.0% 0.0% 20.0% 20.0% 20.0%
1401 RELAY OUTPUT 1 1= READY 1= READY 1= READY 1= READY 1= READY 1= READY 2= RUN
1402 RELAY OUTPUT 2 2= RUN 2= RUN 2= RUN 2= RUN 2= RUN 2= RUN 3= FAULT(-1)
1403 RELAY OUTPUT 3 3= FAULT(-1) 3= FAULT(-1) 3= FAULT(-1) 3= FAULT(-1) 3= FAULT(-1) 3= FAULT(-1) 31 = PFC
1501 AO1 CONTENT SEL 103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT FREQ
1507 AO2 CONTENT SEL 104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
104 =
CURRENT
130 =
PID 1 FBK
1510 MINIMUM AO2 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 4.0 mA
1601 RUN ENABLE 0= NOT SEL 0= NOT SEL 6= DI6 6= DI6 4= DI4 5= DI5 2= DI2
2201
ACC/DEC 1/2 SEL 5= DI50= NOT SEL 5= DI50= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL
3201 SUPERV 1 PARAM 103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT FREQ
3401 SIGNAL1 PARAM 103 = 0103
OUTPUT FREQ
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
102 = 0102
SPEED
103 = 0103
OUTPUT FREQ
4001 GAIN 1.0 1.0 1.0 1.0 1.0 1.0 2.5
4002 INTEGRATION TIME 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 3.0 s
4101 GAIN 1.0 1.0 1.0 1.0 1.0 1.0 2.5
4102
INTEGRATION TIME 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 3.0 s
8123 PFC ENABLE 0= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 0= NOT SEL 1= ACTIVE